产品
Test head HANS - 402066
Test head HANS stainless steel OT 2 1/2"
P max: 60 bar
and equipped with quick couplings and protective caps.
In contrast to the HEINZ specimen, this specimen has two ball valves with quick couplings 5010
and one quick coupling 2510 without ball valve.
A screw coupling -VA- is provided for connecting an external pressure sensor of the smart memo.
文章隶属关系:
Option DVGW W 400-2
Menu-driven pressure test procedures for water pipes according to German DVGW W 400-2
- Contraction procedure
- Accelerated normal procedure
- Normal procedure
- Influence-minimized normal procedure
Option EN 805
Menu-driven test procedures for pressure tests on water pipes according to rules and regulations of EN 805 (Europe):
- Contraction procedure
- Normal procedure
Option service line connection extended
Menu-guided pressure test procedures for gas service lines.
This menu item allows for a combined strength test
(in accordance with German DVGW G 459-1) and subsequent tightness test of gas house
connections with low pressure.
smart memo
Electronic pressure test case for pressure tests
with connection possibility of up to 5 external pressure or temperature sensors.
- the test procedures are menu-guided and can be carried out with
simple Data entry dialog
- a freely programmable pressure test is included
- optional test sequences for gas and water tightness tests
e.g. according to DVGW, ÖVGW, EWE, Avacon, WEVG.
- a subsequent addition of test sequences is possible easily
- large, illuminated display, even in direct sunlight easy to read
- Data entry and signature via touch display and foil keys
- Stylus for the touch display included
- Data memory for hundreds of measurements, depending on
test sequence
- Communication via Bluetooth for update, data transmission, printer
- LTE / GPS module (optional)
- robust case (IP 67)
- Operating time approx. 200 hours, extension with power supply
possible from outside
Dimensions: 220 x 90 x 168 mm
Weight: approx. 1450 g
Test pump MPP 28-25
Test pump MPP 28-25 Pressure range 0 - 25 bar
- practice-oriented test pumps with electronic control unit
for the simplified performance of compression tests pursuant
to EN 805 (W 400-2 in Germany)
- automatic pressure stabilisation for preset test pressure which
can be programmed in steps of 0.1 bar into the control unit
- high delivery capacity rate of 28 l/min enable the generation
of the required test pressure in less than 10 minutes, as required
by the contraction procedure
technical data:
- connection value: 230 V / 400 V 50 Hz
- power consumption: 2.200 VA
- protection type: IP 54
- max. test pressure 25 bar
- test pressure: 0 to 25 bar in steps of 0.1 bar
- safety: safety valve
- delivery volume: 28 l/min
- decompression: automatic / manual
- GSM-remote monitoring: optional
Test pump MPP 68-25
Test pump MPP 68-25 Pressure range 0 - 25 bar
- practice-oriented test pumps with electronic control unit
for the simplified performance of compression tests pursuant
to EN 805 (W 400-2 in Germany)
- automatic pressure stabilisation for preset test pressure which
can be programmed in steps of 0.1 bar into the control unit
- high delivery capacity rate of 68 l/min enable the generation
of the required test pressure in less than 10 minutes, as required
by the contraction procedure
technical data:
- connection value: 400 V 50 Hz
- power consumption: 4.000 VA
- protection type: IP 54
- max. test pressure 25 bar
- test pressure: 0 to 25 bar in steps of 0.1 bar
- safety: safety valve
- delivery volume: 68 l/min
- decompression: automatic / manual
- GSM-remote monitoring: optional
Test pump MPP 68-35
Test pump MPP 68-35 Pressure range 0 - 35 bar
- practice-oriented test pumps with electronic control unit
for the simplified performance of compression tests pursuant
to EN 805 (W 400-2 in Germany)
- automatic pressure stabilisation for preset test pressure which
can be programmed in steps of 0.1 bar into the control unit
- high delivery capacity rate of 68 l/min enable the generation
of the required test pressure in less than 10 minutes, as required
by the contraction procedure
technical data:
- connection value: 400 V 50 Hz
- power consumption: 5.000 VA
- protection type: IP 54
- max. test pressure 35 bar
- test pressure: 0 to 35 bar in steps of 0.1 bar
- safety: safety valve
- delivery volume: 68 l/min
- decompression: automatic / manual
- GSM-remote monitoring: optional
Test pump MPP 11
Test pump MPP 11 Pressure range 0 - 25 bar
full automatic testing pump for pressure build-up and pressure holding adjusted
without pressure impulses
technical data:
- connection value: 230 V 50 Hz
- power consumption: 1.850 VA
- protection type: IP 54
- max. test pressure 25 bar
- test pressure: 0 to 25 bar in steps of 0.1 bar
- safety: safety valve
- delivery volume: 11 l/min. Maximum output approx. 300 l
until automatic switch off, limited by temperature.
- decompression: manual
- Geka connection for water connection
- quick coupling for pressure-side connection
Description
The HANS test head is a device for carrying out pressure tests on gas, water, waste water or other pipelines. It has four practical connections via which the individual steps of a pressure test can be carried out safely and easily: one connection each for pressure build-up and pressure release, one connection for a pressure sensor for pressure measurement, one connection for a control manometer.
The test head has an external thread of 2 ½" and is suitable for pressure tests up to 60 bar. All quick couplings are equipped with protective caps for safety and are thus protected against dirt or water. With the optional test adapters, a tight transition to many threads and fittings is achieved.